TCW220 - Ethernet DAQ Unit with Datalogging and IO Expansion

TCW220 - Ethernet DAQ Unit with Datalogging and IO Expansion
Zoom  Zoom
Our Price:  £169.00(£202.80 Inc. VAT)
Add UK 12V DC Mains PSU:  
Add EU 12V DC Mains PSU:  

Analogue Inputs:  2
Digital Inputs:  2
Digital Outputs:  2
Temperature Inputs:  8

Availability:  

3 in stock, immediate despatch  

3 in stock, immediate despatch

The TCW220 is an Ethernet control unit with 2 digital inputs, 2 relay outputs, 2 analogue inputs and a 1-Wire interface for up to 8 x 1-Wire sensors. The TCW220 has built-in memory and can log up to 36 days worth of data which can be periodically uploaded to a dedicated server by HTTP Post. Also supports alarms via email or SNMP trap and supports XML/JSON and Modbus TCP data communication protocols.


Special Offer:  Discounts of 7%, 10%, 12.5% and 15% are available when you order 10, 25, 50 and 100 items or more of this product.

  • 2 digital inputs with "dry contact" and "logic level" modes
  • 2 analogue inputs with 0 to 10VDC range, 0.001V resolution
  • 2 relays with NO and NC contacts
  • Relay rating: 30VAC, 24VDC, 3A
  • 1-Wire support for up to 8 1-wire sensors - temperature, humidity, carbon dioxide, 4-20mA, AC/DC current
  • Data logger functionality for at least 36 days
  • Log rate adjustable between 10 to 3600 seconds
  • Data can be logged on a time, on alarm or both time and alarm
  • Periodic data upload to dedicated server via HTTP Post
  • Web interface for configuration and monitoring - online  demo >> (admin/admin)
  • Up to 4 graph pages with up to 4 channels per graph
  • SNMP traps on alarm
  • e-mail on alarm - up to 5 email recipients 
  • XML and HTTP API commands
  • Android and Apple IOS Apps
  • NTP protocol support
  • Real time clock for scheduled time/date control
  • Power: 10-32VDC at 300mA
  • Dimensions: 115mm x 90mm x 40mm
  • Operating temperature: -20°C to +70°C
  • DIN Rail mount enclosure

The TCW220 is a general purpose Ethernet data logger for data acquisition applications. It has 2 analogue inputs, with 10-bit resolution and 2 digital  inputs. It utilizes 1-Wire interface for up to 8 x 1-Wire sensors – carbon dioxide, 0/20mA, AC/DC current, temperature, humidity etc.) The Ethernet data logger also has 2 relays with normally open and normally close contacts.

All monitored parameters can be logged on previous set time interval and/or on alarm condition. The memory is large enough for at least 36 days with records on every 1 minute. Log file can be periodically uploaded on dedicated server by HTTP Post.

XML/JSON file with all monitored parameters can periodically uploaded on dedicated server by HTTP Post. Like answer server can return commands for relay’s control. This is a way for building SCADA system.

The relays can be activated either remotely (WEB, SNMP, HTTP, MODBUS etc.) or locally – from status of monitored parameters. For every parameter e-mails and SNMP traps for up to 5 recipients can be sent. Alarm alert also can be sent by HTTP Post with XML/JSON status files.

TC Monitor Software

TC Monitor is easy to use Windows application for monitoring and control of TCW products. TC Monitor can collect and display data from controllers installed in different locations (sites). The collected data is stored in SQL database and can be displayed or exported in MS Excel format for further analysis. TC Monitor has a simple web interface, which enables easy and fast configuration. Monitored parameters can be 1-wire sensors, digital and analog inputs and relay outputs.

The free version of TC Monitor provides 10 credits, this means up to 10 different parameters can be monitored and logged. More Information >>

Optional Software

Profilab

ProfiLab-Expert is a low cost graphical programming software package for data acquisition and control applications. No programing experience is needed, programs are written by connecting function blocks together with wires. Professional user panels can be designed with custom controls, and the whole program can be compiled into a stand-alone executable file, with no run-time penalties.

More Information >>


Downloads

User Manual >>

TCW Discover Utility >>

SNMP MIB Table >>

TC Monitor Manual >>