A
low cost 3 or 6 channel analogue input LCD chart recorder with
alarms, digital inputs, Relay outputs, analogue outputs, Ethernet and
RS232 comms with MODBUS protocol, maths functions. Analogue data can
be displayed as trends, bar charts or numeric displays. Data is
recorded on CF memory cards.
|
|
The
VR06 is a panel mounted LCD chart recoder with alarms, maths
functions and MODBUS based serial communications. Available as 3 or 6
channel analogue input models. There are 4 expansion slots for
addition digital I/O cards. Virtually any sensor can be connected to
the analogue inputs, thermocouples, PRT, mV, V, 4-20mA etc.

The
VR06 stores data to a supplied 128M Compact Flash memory card at
pre-set rates - 1, 2, 5, 10, 30, 60 or 120 seconds. Other sizes of CF
memory card can be fitted up to 1G. The VR06 can also display channel
data in real time in various formats on up to 6 different pages. This
can be scrolling charts, bar charts, numeric display, or a
combination of all in "Mixed mode".

Recorded
data can also be recalled and displayed in "History" mode.
Each
analogue input can be programmed with 2 sets of high/low/deviation
alarms, and 2 seperate events can be instigated on alarm. This could
be seting a relay output or generating a report. The VR18 also
supports virtual channels, whereby a channel can be derrived from
several others using a maths function. The digital inputs can also
generate alarms or events. Alarms can be display and acknowledged on
the larm List page.

The
VR06 also has up to 6 counter/timer/totalize functions.
Timer/counter functions can be used to generate reports at specific
times on a daily, weekly or monthly basis. The totalizer is useful
for compling data for inclusion into reports.
The
VR06 comes with an Ethernet port as standard and can be fitted with
an RS232/485 port as an optional extra. The VR06 supports MODBUS RTU,
and can easily integrate with any existing SCADA package. The VR18
also comes with the Observer software package whcih allows
configuration, monitoring and data downloading.
|
|
Power
Display
Memory
Analogue
Input Card
-
Resolution:
18 bits
- Sampling
Rate: 5 times/ second
- Maximum
Rating: -2 VDC minimum, 12 VDC maximum (1 minute for mA input)
- Common
Mode Rejection Ratio (CMRR): 120dB
- Normal
Mode Rejection Ratio (NMRR): 55dB
- Isolation
Breakdown Voltage between channels: 430VAC min.
- Sensor
Break Detection: Sensor opened for TC, RTD and mV inputs, below 1 mA
for 4-
- 20mA
input, below 0.25V for 1-5V inputs, unavailable for other inputs
- Sensor
Break Responding Time: Within 10 seconds for TC, RTD and mV inputs,
0.1 second
- for
4-20 mA and 1-5V inputs
|
Sensor
Type |
Range |
Accuracy
@ 25°C |
Input
Impedance |
|
J |
-120
to 1000°C |
±1°C |
2.2M |
|
K |
-200
to 1370°C |
±1°C |
2.2M |
|
T |
-250
to 400°C |
±1°C |
2.2M |
|
E |
-100
to 900 °C |
±1°C |
2.2M |
|
B |
0
to 1820°C |
±2°C |
2.2M |
|
R |
0
to 1767°C |
±2°C |
2.2M |
|
S |
0
to 1767°C |
±2°C |
2.2M |
|
N |
-250
to 1300°C |
±1°C |
2.2M |
|
L |
-200
to 900°C |
±1°C |
2.2M |
|
PT100
(DIN) |
-210
to 700°C |
±0.4°C |
1.3k |
|
PT100(JIS) |
-200
to 600°C |
±0.4°C |
1.3k |
|
mV |
-8
to 70mV |
±0.05% |
2.2M |
|
mA |
-3
to 27mA |
±0.05% |
70.5 |
|
0-1V |
-0.12
to 1.15V |
±0.05% |
32k |
|
0-5V |
-1.3
to 11.5V |
±0.05% |
332k |
|
1-5V |
-1.3
to 11.5V |
±0.05% |
332k |
|
0-10V |
-1.3
to 11.5V |
±0.05% |
332k |
Digital
Input Card
-
Channels:
6 per card
- Logic
Low: -30V minimum, 0.8V maximum
- Logic
High: 2V minimum, 30V maximum
- External
Pull-down Resistance: 1K
Digital
Output Card
-
Channels:
6 per card
- Contact
Form: N.O. (form A)
- Relay
Rating: 5A/240 VAC, life cycles 200,000 for resistive load
COMM
Module
Standard
Ethernet Communication
Infrared
Detector
Environmental
& Physical
Approval
Standards
-
Safety:
- UL873
(11th edition, 1994),CSA C22.2 No. 24-93
- EN61010-1
(IEC1010-1) Over voltage category II, Pollution degree 2
- Protective
Class:
- IP
30 front panel for indoor use,
- IP
20 housing and terminals
- EMC
- Emission:
EN50081-1, EN61326
- (EN55011
class B, EN61000-3-2, EN61000-3-3)
- Immunity:
EN50082-2, EN61326 (EN61000-4-2, EN61000-4-3,
- EN61000-4-4,
EN61000-4-5, EN61000-4-6,
- EN61000-4-11,
EN50204)
Event
Options
-
No
Action: Do nothing.
- Log
Alarm: Record alarms
- Log
Event: Record events
- Sound
Buzzer: Sound the buzzer. It stops once any key is pressed.
- Set
DO On: Set digital output / relay on, and then select Target from
DO1 to DO 6.
- Set
DO Off: Set digital output / relay off, and then select Target from
DO1 to DO 6.
- Enable
Timer: Start the timer, and then select Target from Timer1 to Timer6.
- Disable
Timer: Stop the timer, and then select Target from Timer1 to Timer6.
- Preset
Totalz: Start the totalizer with a preset value, then select Target
from Tolz1 to Tolz6.
- Reset
Totalz: Reset totalizer into zero, and then select Target from from
Tolz1 to Tolz6.
- Enable
Totalz: Start the totalizer, then select Target from Tolz1 to Tolz6.
- Disable
Totalz: Stop the totalizer, then select Target from Tolz1 to Tolz6.
- Preset
Counter: Start the Counter with a preset value, then select Target
from Cont1 to Cont6.
- Reset
Counter: Reset the counter into zero, and then select Target from
Cont1 to Cont6.
- Inc
Counter: Increase the counter, and then select Target from Cont1 to Cont6.
- Dec
Counter: Decrease the counter, and then select Target from Cont1 to Cont6.
- Log
Report: Make the report for Counter and Totalizer.
Mathematics
Functions
+
Addition
-
Subtraction
*
Multiplication
/
Division
SIN(x)
sin(x)
COS(x)
cos(x)
EXP(x)
ex
SQRT(x)
Square root of x
LN(x)
loge(x)
TG(x)
tan(x)
CTG(x)
1/tan(x)
ASIN(x)
Sin-1(x)
ACOS(x)
Cos-1(x)
ATG(x)
Tan-1(x)
LOG(x)
log10(x)
ABS(x)
Absolute of x
SQ(x)
x2
ROUND(x)
The closest integral number to x
HI(x,y)
The bigger value between x and y
LO(x,y)
The smaller value between x and y
INV(x)
1/x
PCT(x,Hi,Lo)
PCT % = x / Hi-Lo, x: Target Value, Hi: High Value, Lo: Low Value
x%y
Remainder of x/y
x^y
xy
|