Low-cost Modbus RS485 based remote IO units, which provide a simple way for integrating analogue or digital signals to supervisory SCADA systems. The MBIO-8TCS can accept 8 thermocouples.


Special Offer:  Discounts of 7%, 10%, 12.5% and 15% are available when you order 10, 25, 50 and 100 items or more of this product.

  • 8 x Isolated Thermocouple Inputs
  • TC Types - J,K,E,T,N,B,S,R,mV,C,D and G
  • Resolution 0.1 Deg.C
  • Sample rate - 0.63 samples/sec
  • Isolation (Field & Logic) - 1500VAC RMS
  • Isolation (Inter Channel) - 350VAC (Pk to Pk)
  • Operating Temperature. -10°C to + 50°C
  • Power Supply - 12-24V DC (30mA @12V, 17mA @24V)
  • Dimensions - 100mm x 90mm x 25mm (excluding screw terminals)

The MBIO-8TCS module is a 8 isolated thermocouple input module. The module uses differential inputs to reduce effects of electrical noise and mains pickup. The thermocouple inputs are isolated from the logic and from each other. This module is operated in an identical way to the PM8TC module and is fully interchangeable.

The thermocouple voltage is read by the module circuitry, linearised and converted to degrees Centigrade. No ranging is required as the module covers the full range as indicated in the TC table. The value that is read from the Modbus register is the actual temperature in degrees centigrade to 0.1°C resolution. ie: a value of 3451 corresponds to a temperature of 345.1°C.

The module has built in Cold Junction Compensation. Use must be made of the correct thermocouple extension wire to avoid reading errors.

The thermocouple module can also be configured for a 0 - 50mV input range. The TC Type register must be set to 9 for this option. The value in the register which is read back over the network is 0 - 50,000.

Configuration Software

IOStudio is a free software package used to configure the communication settings for IO modules on the Modbus network. Once a module is detected, it is possible to view real-time data of the module directly on the PC and it can be used for diagnostic purposes as well.

 


Downloads

User Manual >>

IOStudio Config Software >>