MBIO-16DI - 16 Channel Digital/Counter Input

MBIO-16DI - 16 Channel Digital/Counter Input
Zoom  Zoom
Our Price:  £99.00(£118.80 Inc. VAT)

Digital Inputs:  16

Availability:  

4 in stock, immediate despatch  

4 in stock, immediate despatch

Low-cost Modbus RS485 based remote IO units, which provide a simple way for integrating analogue or digital signals to supervisory SCADA systems. The MBIO-16DI has 16 opto-isolated digital inputs that can also be used as 32-bit counters.


Special Offer:  Discounts of 7%, 10%, 12.5% and 15% are available when you order 10, 25, 50 and 100 items or more of this product.

  • 16 Digital Inputs
  • 16 Digital Counters
  • Counter Resolution - 32 Bit
  • Counter frequency - 1 KHz (max)
  • Counter Mode - UP or UP/DOWN
  • Digital input 0 level - 0 to +6.5Vdc
  • Digital input 1 level +12Vdc to +24Vdc
  • Input Impedance - 2200 ohms
  • Isolation (Field & Logic) - 1500 V RMS
  • Status Indication - LED per channel
  • Operating Temperature. -10°C to + 50°C 
  • Power Supply - 12-24V DC (30mA @12V, 17mA @24V)
  • Dimensions - 100mm x 90mm x 25mm (excluding screw terminals)
The MBIO-16DI module is a 16 channel digital input module. The inputs are isolated from the logic by bi-directional opto-couplers. The inputs are divided into 2 isolated groups of 8 inputs each. This allows for many configurations in which the input module may be used. One such configuration could be where one group is connected as common positive and the second group connected as common negative.

The counters operate in three modes.

In mode 0: All the counters are disabled.

In mode 1: The counters are 32 bit counters allowing a count value from 0 to 4294967295. The count value can be cleared by writing a zero to the associated registers or preset to any other value using the same method.

In mode 2: The inputs are connected as up/down counters. Input 1 will increment counter 1 whilst input 2 decrements counter1. In the same way, inputs 3&4 operate counter 2, inputs 5&6 operate counter 3 and inputs 7&8 operate counter 4,etc.

When the input filter is configured for > 10ms (Input Filter > 1), then the 16 counters are saved in non-volatile memory and the count value will be saved when the power fails.

The format of the registers allows the status of the inputs to be read as either single bits or all at once as a single register on the Modbus network.