TEMP-485
RS-485 Temperature Sensor
|
|
Description |
|
|
|
|
|
The
Temp-485 device is a temperature sensor which communicates over the
RS-485 bus. The measured temperature is transmitted over a simple
text protocol in °C. Up to 26 sensors can be connected on a
4-wire bus. Two wires are used for the RS-485 bus, the other two to
power the sensor. The RS-485 bus line can be as long as 1200 m.
|
|
Product |
|

TEMP-485
User
Manual >>
|
|
|
Description |
|
|
|
|
|
|
The
Temp-485 device is a temperature sensor which communicates over the
RS-485 bus. The sensor is designed for indoors vertical wall mounting.
The
measured temperature is transmitted over a simple text protocol in
°C. Up to 26 sensors of this kind or 32 sensors at all can be
connected on a 4-wire bus. Two wires are used for the RS-485 bus, the
other two to power the sensor. The sensors can be powered from an
external independent power source and can be connected only with the
remaining wires of the RS-485 bus. The RS-485 bus line can be as long
as 1200 m.
The
sensor uses a semi-conductive element situated inside the metal rod
to measure the temperature. The element measures with an accuracy of
± 0,5°C. The sensor is equipped with an indicator, which
blinks to signalize the measurement of the temperature in progress.
To
minimize the heat losses from the power supply and to have more
possibilities of powering the sensor is equipped with a switching
power supply, which makes possible to connect the sensor with a wide
range of voltage supplies.
The
sensor is equipped with a termination resistor for the RS-485 line,
but the connection with it is controlled by the built-in jumper
RS485 Terminator. It is necessary to insert this jumper
only in the last sensor, where the RS-485 line ends.
|
|
Communication
protocol |
|
|
|
The
sensors operate in a question-answer mode. The maximum response time
is 50 ms.
Temperature
reading
Temperature
request - T<address>I for example send "TAI"
Answer
from sensor (all OK) *<address><temp><CR> *A+025.51C
Answer
from sensor (error) *<address>Err<CR> *AErr
where
<address>
is a character from A... Z with exception of T
<CR>
is the 0xD or 13 decimal - Carriage Return
<temp>
has the format *A+025.5C or *A+025.55C
|
|
Optional
Accessories |
|
|
|
RS485
Converters
A
wide range of converters to enable you to create an RS485 network
from either RS232, USB or Ethernet connections
|
|
 |
SC-101
Budget level RS232 to RS422/485 Converter |
|
|
 |
SC-101-I
Industrial RS232 to
RS422/845. 3000V Isolation |
|
|
 |
USB-101
Budget
level USB to RS422/485 Converter |
|
|
 |
USB-101-I
Industrial USB to
RS422/845. 3000V Isolation |
|
|
|
|
|
|
|
 |
eNET-232 Budget
level Ethernet to RS422/485 Converter |
|
|
 |
eNET-432
- 2-port Ethernet to
RS422/485 Converter |
|
|
 |
eNET-P132W
Wireless Lan 802.11 Ethernet
to RS422/485 Converter |
|
|
|
|
|
|
|
|
Software |
|
|
|
|
|
|
|
DAQFactory
SCADA Package
Control
and monitoring software DAQFactory
can be used with eDAM 9000 units. DAQFactory can be used to create an
opertor interface, with plant mimics, chart recorders, provide
automatic control, PID loops, alarms and datalogging and reporting functions.
|

|
|