Home Page

Contact Us

My Basket

Checkout

PCX-4264 PCI Digital I/O Card


Description

 
The PCX-4264 is isolated digital input and output card with 32 open collector transistor outputs and 32 opto-isolated inputs. The PCX-4264 features channel-to-computer isolation of upto 5000 Vdc to offer protection against damage caused by accidental contact with high voltages and it eliminates troublesome ground loops. Supplied with a DLL, an ActiveX and drivers for use with LabView and InTouch SCADA software.

 

Click to enlarge

New Lower Price

User Manual >>

 

  • 32 Open-Collector output channels

  • 32 Optical isolated digital input channels
  • Built-in internal DC-DC conveter for detecting dry contacts
  • on-board software programmable digital debounce
  • Software programmable Interrupt handling for 16 input channels
  • Requires 1 off 8068 screw terminal panel and cable
  • Visual Basic, C++ Delphi examples plus drivers for LabVIEW, InTouch and DAQFactory

 

Specifications

 

Optical Isolated Input Channel

  • Numbers of Channel: 32 digital inputs

  • Input polarity: polarity sensitive for PCX-4264
  •  Digital debounce - software programmable from 10msec to 160 msec
  • Input Voltage: 0 - 24V dc
  • Logic H: 3~24V
  • Logic L: 0~2.4V
  • Input resistance: 4.7kohm @ 0.5W
  • Isolated voltage: 5000 Vrms
  • Throughput: 10K Hz (0.1 ms)
  • Channel 0 to channel 7 can generate an interrupt

Environmental

  • Power requirements +5V 460mA (typical)

  • Operation Temp :0° C~50° C
  • Storage Temp :-20° C~70° C
  • Humidity :0 to 90% none-condensing
  • Dimensions :172 X 120 mm

 

Optical Isolated Output Channel

  • Numbers of Channel: 32 digital outputs

  • Output type: Darlington transistors with common ground
  • Output voltage: 5VDC min, 90VDC maximum
  • Output Device:ULN2803(common ground)
  • Sink Current: Max. 500mA/ch for only one of the ULN2803 transistor is ON
  • Power Dissipation: 1.47W per ULN2803 device (8 channels)
  • Isolated voltage: 5000 VDC

Software

 
Included with each card;

  • Software Toolkit (DLL, ActiveX) for Windows 98/2000/NT/XP

  • Many Visual Basic, C++, Delphi etc. examples
  • Software Toolkit for Labview, Wonderware Intouch
  • DAQFactory Driver and examples

Control and monitoring software DAQFactory can now be used with up to 4 cards. DAQFactory can be used to create an opertor interface, with plant mimics, chart recorders, provide automatic control, PID loops, alarms and datalogging and reporting functions.

 

 

Accessories

 

8068 Screw Terminal Board + Cable



 

 

  • Optional 8068 68-way SCSI to screw terminal board.

  • 1m 68-way SCSI ribbon cable Included

 

 

Phone +44(0)115 925 8412 | Fax +44(0)115 925 9757